V9 SERIES PRESSURE FIRED
BOILER-BURNER UNIT
SUGGESTED SPECIFICATIONS
Note: To use as a project specification:
A. Insert, in the blank spaces provided, the applicable model number, capacity,
fuel, and electrical data.
B. Delete the item in parentheses or marked “*” which are not applicable to the
project requirements.
C. Insert, where applicable, optional non-standard features desired.
1. GENERAL SPECIFICATION
Contractor shall furnish and install, where indicated on the drawings, ______ (quantity) Model
V-9______A, ______ (steam or water), ______ (#2 Oil, Nat. or LP Gas, #2 Oil and Nat. or LP Gas)
pressure fired boiler-burner unit(s), having an I=B=R approved gross output of ______ MBH per boiler
and a net rating of ______ MBH with an I=B=R burner capacity of _______ MBH (Gas) ______ GPH
(#2 Oil). Boiler(s) shall be constructed of cast iron sections manufactured in accordance with ASME
requirements for low pressure boilers and each section shall be permanently marked with the ASME
symbol and the maximum allowable working pressures. The boiler-burner unit shall not require a
refractory combustion chamber and the sections shall be of wet base construction. Further, the boiler-
burner unit shall be designed so that only a vent shall be required that extends only 3 feet above the
highest point of the roof.
2. BOILER EQUIPMENT SPECIFICATION
*2.1 The boiler shall be furnished as a knocked down unit for field erection according to the
manufacturer’s instructions.
*(NOTE TO SPECIFIER: The V9 boiler-burner unit is shipped as standard with sections
unassembled. However, if job conditions permit, the following options are available.
*2.2 The boiler shall be furnished as a factory assembled and water tested section assembly with the
jacket, burner, and controls shipped separately.
*2.3 The boiler shall be furnished as a factory packaged boiler with jacket, burner, and controls
mounted and wired. Boiler shall be mounted on a steel shipping skid and entire package shall
be shrink wrapped.
*2.4 Factory packaged boiler shall be factory firetested.
2.5 Boiler shall be equipped with a flange mounted flame retention forced draft burner that has been
designed and tested for a minimum of 82% (Gas fired) and/or 84% (Oil fired) combustion
efficiency based on I=B=R testing procedure.
2.6 The boiler-burner mounting plate shall be lined with lightweight refractory insulation and shall
have built-in observation port with closure cover.
2.7 Boiler sections shall have pin-like projections on each center section, evenly spaced on the
vertical flue surfaces to extract the greatest possible heating value from the hot flue gases.
2.8 Boiler sections shall be surface ground to ensure smooth positive mating surfaces.
2.9 Boiler sections shall be assembled with precision machined cast iron push nipples, pressed into a
mating machined nipple port in the section eliminating the need for any gasket material which would
be subject to deterioration due to corrosion or oil based chemicals. The sections are to be assembled
with short draw rods.
2.10 A gas-tight seal, which is imperative for forced draft boilers, will be achieved with the
application of a silastic sealant in a finished ground groove between sections.
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - V9 SERIES PRESSURE FIRED

V9 SERIES PRESSURE FIRED BOILER-BURNER UNIT SUGGESTED SPECIFICATIONS Note: To use as a project

Seite 2

2.11 Washout tappings shall be provided in both the front and back boiler sections. Blowoff tapping shall be provided in the back boiler

Seite 3

(b) shall be manual reset type suitable for 115 volt 60 Hz. 3.2 A separate operating control shall be furnished by the

Seite 4

- The burner shall be arranged for (on-off) (low-high-off) (low-high-low) (full modulation with manual potentiometer) operation. - The