for Commercial Boiler Applications
www.commercialcastiron.com
The Burnham Commercial RTC Return Temperature Control provides an economical and effective means of boiler
protection from thermal shock and sustained condensing operation. The RTC monitors the boiler return water
temperature and operates a 3-way diverting valve and boiler circulator to maintain a minimum return temperature
of 135°F or greater. An outdoor reset function is also available to reset the system water temperature based on
outdoor air temperature. Studies indicate that resetting the boiler and system water temperature increases effi-
ciency and reduces operating costs. The controls is available in two configurations: Basic RTC Kit and RTC kit with
Outdoor Reset Control.
Return Sensor
Monitors Boiler Return
Water Temperature
RTC
Return Temperature Control
Includes:
Outdoor Reset option
LCD display of return
water temperature
3-way
Diverting
Valve
Boiler
Circulator
Maintains
Minimum 135°F
Return Water
Temperature
1
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1

for Commercial Boiler Applicationswww.commercialcastiron.comThe Burnham Commercial RTC Return Temperature Control provides an economical and effectiv

Seite 2 - RETURN TEMPERATURE CONTROL

2The concept of boiler protection has existed for many years. However, the primary focus in hydronic systems is often the demand and delivery design c

Seite 3 - RTC Kit Selection Chart

3www.commercialcastiron.comRTC Kit Selection Chart (1)SELECT BOILER SIZE BASED ON ∆ T (4)VALVE SIZE(1) (2) BASIC RTC KITPART #RTC KIT w/OUTDOOR RES

Seite 4 - ∆ T Circulator Sizing

20° ∆ T Circulator Sizing (1)www.commercialcastiron.com©2011 Burnham Commercial - Lancaster, PA2www.burnhamcommercialcastiron.comForm No. PL814657010