For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide
Boiler Model Number and Serial Number as shown on Rating Label.
Boiler Model Number
30__B
Boiler Serial Number Installation Date
Heating Contractor Phone Number
Address
INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
SERIES 3™
Gas - Fired Boiler
Seitenansicht 0
1 2 3 4 5 6 ... 55 56

Inhaltsverzeichnis

Seite 1 - SERIES 3™

103796-04 - 3/139700609Price - $5.00For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide Boil

Seite 2 - WARNINGS FOR THE HOMEOWNER

102. Screw the water supply manifold into the boiler outlet tapping “O.”3. Orient the manifold with the relief valve on top.4. Screw the relief val

Seite 3 - What's in the crate?

117. Screw an installer-supplied 1¼” pipe or nipple into the water return tapping “R”.8. Screw the supplied drain valve into tapping “D”.6. CONNECT

Seite 4 - SPECIFICATIONS

12 DISCONNECT ELECTRICAL POWER to the boiler and heating system before servicing. Positively assure that no voltage is present. Lock ele

Seite 5 - SPECIFICATIONS (continued)

138. PROGRAM THE CONTROLSIntelligent Hydronic Control8-bIQ Option Panel8-aUsing Intelligent Hydronic Control DisplayThe Intelligent Hydronic Control

Seite 6 - BOILER QUICK-START

148. PROGRAM THE CONTROLS (continued)Please note that in operating mode to hold the display on the value the user can press and hold either the Up ñ

Seite 7 - 1. UNPACK THE CRATE

158. PROGRAM THE CONTROLS (continued)Table 8a: Circulator Pre-purge Time example, (PP_ = 2 minutes)Call for Heat SourceDHW Terminal Se

Seite 8 - CAUTION

16b. When dh_ is set equal to Second Heating Zone (tt2) When there is no IWH the “DHW Circulator” output may be congured to control a second heatin

Seite 9 - 4. CONNECT VENTING

1710-b10. PERFORM STARTUP CHECKS AND ADJUSTMENTS FAILURE TO PERFORM THESE CHECKS of the boiler's combustion and safety systems may

Seite 10 - 5. CONNECT GAS PIPING

18ANNUAL MAINTENANCE CHECKLIST WARNINGSTHE BOILER CONTAINS REFRACTORY CERAMIC FIBER, a possible human carcinogen Use a NIOSH approved respirator whe

Seite 11 - Item Description Part Number

19Before troubleshooting The following pages contain trouble shooting tables for use in diagnosing control problems. When using these tables the fo

Seite 12 - 7. CONNECT ELECTRICAL WIRING

2FOLLOW ALL INSTRUCTIONS and warnings printed in this manual and posted on the boiler.INSPECT THE BOILER ANNUALLY. To keep your boiler safe and efcie

Seite 13 - 8. PROGRAM THE CONTROLS

20TROUBLESHOOTING (continued)Use Control Display ERR (error) Number To Direct Troubleshooting Efforts If the control detects an error it will ash “E

Seite 14

21TROUBLESHOOTING (continued)Use STA (status) Number To Guide Troubleshooting The control will ash “STA” followed by a number. Use this number to

Seite 15

226. Circulator is On, Damper is Open But Boiler Fails to Start Display / Status DescriptionSTA 10Retry / RecycleDelayThe Boiler is in “Retry Delay”

Seite 16

23Display / StatusRecommended Corrective ActionStA 10Retry / Recycle DelayStA 13Soft Lockout1. No Spark a. Can you hear sparking while STA 6 is

Seite 17

24TROUBLESHOOTING (continued)If Control Shows Status Code “STA 15": The control is “Waiting for Limit to Close” and the display on the IQ Optio

Seite 18 - WARNINGS

25REPAIR PARTS LISTKey No.Description[Quantity] Part Number 303B 304B 305B 306B 307B 308B 309B1A Block Assembly 102287-03 102287-04 102287-05 102287-0

Seite 19 - TROUBLESHOOTING

26REPAIR PARTS LIST (continued)Key No.Description[Quantity] Part Number 303B 304B 305B 306B 307B 308B 309B2A Base Wrapper 71807031 71807041 71807051 7

Seite 20 - TROUBLESHOOTING (continued)

27REPAIR PARTS LIST (continued)Key No.Description[Quantity] Part Number 303B 304B 305B 306B 307B 308B 309B3AGas Valve (Natural Gas), Honeywell VR8204P

Seite 21 - Display / Status

28REPAIR PARTS LIST (continued)Key No.Description[Quantity] Part Number 303B 304B 305B 306B 307B 308B 309B4A Control 103660-014B IQ Option Panel 10229

Seite 22

29Key No.Description[Quantity] Part Number 303B 304B 305B 306B 307B 308B 309B5A Jacket Left Side Panel 102566-015B Jacket Right Side Panel 102567-015C

Seite 23

3Congratulations on your purchase of a new Series 3™ boiler—designed and constructed to provide you with years of reliable service. • ENERGY STAR™

Seite 24

30REPAIR PARTS LIST (continued)Key No.Description[Quantity] Part Number 303B 304B 305B 306B 307B 308B 309B6A Supply Water Manifold 806070016B Temperat

Seite 25 - REPAIR PARTS LIST

31INTERNAL WIRING Figure IW-1: Wiring Diagram

Seite 26 - REPAIR PARTS LIST (continued)

32INTERNAL WIRING (continued)Figure IW-2: Wiring Schematic

Seite 27

33INTERNAL WIRING (continued)Figure IW-3: Multiple Zone System with Zone CirculatorsFigure IW-4: Multiple Zone System with Zone Valves

Seite 28

34INTERNAL WIRING (continued)Figure IW-5: Multiple Zone System with Zone Circulator PanelT STAT 1VALVE 1T STAT 2VALVE 2T STAT 3OFFONZONE 4 PRIORITYTA

Seite 29

35APPENDIX A – COMBUSTION AIR PROVIDE ENOUGH AIR to ventilate the boiler room, dilute the ue gases, and sustain combustion. Ignition fail

Seite 30

36APPENDIX B – VENTING VENT THIS BOILER according to the instructions. Failure to do so may cause products of combustion to enter the buil

Seite 31 - INTERNAL WIRING

37 Au moment du retrait d’une chaudière existante, les mesures suivantes doivent être prises pour chaque appareil toujours raccordé au système d’eva

Seite 32 - INTERNAL WIRING (continued)

38APPENDIX B1 – ATMOSPHERIC VENTINGFigure B-1: Typical Atmospheric Vent Installation GENERAL WARNINGS FOR ATMOSPHERIC VENTING SYSTEMSUSE ATMOSPHERI

Seite 33

39N’ÉVACUEZ LES PRODUITS DE LA COMBUSTION DU GAZ DANS L’ATMOSPHÈRE que dans le cas de chaudières approuvées pour cela comme le stipule la section Spéc

Seite 34

4 Series 3Boiler ModelInput (MBH) DOE Heating Capacity (MBH) Net AHRI Rating (MBH) AFUE (%)303B 70 59 51 84304B 105 8

Seite 35 - APPENDIX A – COMBUSTION AIR

40APPENDIX C – GAS PIPING ASSURE GAS PIPING IS LEAK FREE AND OF PROPER SIZE and type for the connected load. SHUT OFF MAIN GAS SUPPLY

Seite 36 - APPENDIX B – VENTING

415. Bond all above-ground gas piping to a grounding electrode and ensure the piping is electrically continuous. DO NOT USE GAS PIPING AS A

Seite 37

423. Overpressure(1) Install a properly sized expansion tank. (2) Do not exceed the boiler’s specic requirements for maximum allowable working

Seite 38

43APPENDIX D – System Piping (continued)Figure D-W2: Recommended Water Piping for Zone Valve Zoned Heating Systems

Seite 39

44APPENDIX D – System Piping (continued)Figure D-W3: Recommended Water Piping for Circulator Zoned Heating Systems

Seite 40 - APPENDIX C – GAS PIPING

45APPENDIX E – FILLING THE SYSTEM AND CHECKING FOR LEAKSFill entire heating system with water and vent air from system. Use the following procedure o

Seite 41 - APPENDIX D – SYSTEM PIPING

46APPENDIX F – ADJUSTING GAS INPUT RATECheck Manifold Pressure:1. Note the rated manifold gas pressure listed on the boiler’s rating label.2. Connec

Seite 42

47APPENDIX G – CHECKING DRAFT AND COMBUSTIONCHECK DRAFT (GAS BOILERS WITH DRAFT HOODS)1. Insofar as is practical, close all doors and windows in the

Seite 43

48APPENDIX H – OPERATIONBoiler Sequence of OperationNORMAL OPERATION1. The boiler is equipped with an Intelligent Hydronic Control (control). This c

Seite 44

49APPENDIX I – IQ CONTROL SYSTEMIQ Control System Overview The “IQ Control System” consists of a control and an IQ Option Panel with optional “plug in

Seite 45

5Figure S-1: Minimum Clearances to Combustibles and Alcove DimensionsSPECIFICATIONS (continued)

Seite 46

50APPENDIX I – IQ Control System (continued)IQ Outdoor Reset Option Card: P/N 102723-01 Installing the IQ Outdoor Reset Option Card is the simplest

Seite 47

51APPENDIX I – IQ Control System (continued)IQ High Limit Option Cards add auxiliary temperature limit-rated controls to boilers. High Limit Option C

Seite 48 - APPENDIX H – OPERATION

52APPENDIX I – IQ Control System (continued)Part Number Item Description102723-01Outside Reset IQ Option Card, Domestic Hot Water Priority, for use wi

Seite 49

53SERVICE RECORDDATE SERVICE PERFORMED

Seite 50

54SERVICE RECORDDATE SERVICE PERFORMED

Seite 51

55SERVICE RECORDDATE SERVICE PERFORMED

Seite 52 - Additional Information List

56U.S. Boiler Company, Inc.P.O. Box 3020Lancaster, PA 176041-888-432-8887www.usboiler.net

Seite 53 - SERVICE RECORD

6Installation: 1. Unpack the crate ... 7 2. Position th

Seite 54

7 THE BOILER IS TOP-HEAVY. Do not allow it to tip over.1. Remove the sleeve. 2. Remove the contents from the skid, except the boiler.3

Seite 55

82. POSITION THE BOILER WARNINGS1. Slide the boiler into desired location.2. Meet the minimum clearances to combustible construction per the Speci

Seite 56 - 1-888-432-8887

93. PROVIDE COMBUSTION AIR INSUFFICIENT COMBUSTION AIR SUPPLY may result in the production and release of deadly carbon monoxide (CO)